Consumer piping not adequately supported

Advisory note05/2023
ForLicensees and contractors working in the gasfitting industry
ScopeApplies to all areas in New South Wales

Issue

Recent gas audit inspections of Class 1 and 2 buildings carried out by Fair Trading’s Gas Compliance Unit have identified piping not adequately supported in gas installations.

All gas installations in NSW must comply with the Gas and Electricity (Consumer Safety) Act 2017 with any installation not conforming to AS/NZS 5601.1:2022 considered non-compliant.

Reference

Gas and Electricity [Consumer Safety] Regulation 2018

AS/NZS 5601.1:2022 - Gas Installations

4.5.2 – Installation of proprietary systems

Proprietary systems shall be installed in accordance with TABLE 4.2 and the relevant manufacturer’s instructions.

5.8.1 – Consumer piping support system requirements

The consumer piping support system shall –

(a) be capable of supporting the piping system;

(b) firmly restrain the piping in the intended position and control movement of the piping system, taking into account any seismic requirements where appropriate; and

(c) have any component of the supporting system, which is to be in contact with the pipe, made of material that is compatible with the consumer piping material or electrically isolated from such piping system or equipment.

5.8.2 – Spacing of supporting devices

The spacing of supporting devices shall not exceed those specified in TABLE 5.8.2 or shall be in accordance with the piping manufacturer’s instructions. See Table 5.8.2 below.

Table 5.8.2 - Spacing of supporting devices

Nominal size of pipe
DN

Vertical or horizontal run spacing, m

Steel pipe
Copper or stainless
steel pipe
Semi-rigid stainless
steel pipe
Multilayer pipe
8
10
12
2
2
-
1
1.5
-
-
-
0.5
-
-
0.75
15
18
20
2
-
2.5
1.5
1.5
1.5
0.5
-
0.5
1
-
1.25
25
32
40
2.5
3
3
2
2.5
2.5
0.5
0.5
-
1.5
2
2
50 - 65
80 - 200
3
4
3
4
-
-
2
-

Requirements

All gas consumer piping must be installed with adequate support as per the requirements AS/NZS 5601.1 2022 and the relevant manufacturer’s installation instructions.

Below are example photos of identified non-compliant installations.

Image example 1: The multilayer gas pipe is installed without adequate support and the separation between clips is over the maximum permitted distance

Example 1: The multilayer gas pipe is installed without adequate support and the separation between clips is over the maximum permitted distance

Image example 2: The multilayer gas pipe is installed without adequate support and the separation between clips is over the maximum permitted distance

Example 2: The multilayer gas pipe is installed without adequate support and the separation between clips is over the maximum permitted distance

Image example 3: The separation between clips of an installed multilayer pipe is over the maximum permitted distance

Example 3: The separation between clips is over the maximum permitted distance.



For more information, please email: [email protected]

This advisory note has been approved for issue by the BSCU Technical Review Committee. Information contained within this document is current as of January 2023 and refers to codes and standards current at the time of writing.

NSW Fair Trading disclaims any liability (including for negligence) to any person in respect of anything done, or not done, by that person in whole or partial reliance on any of the information in this advisory note.

Prev Sizing a consumer gas service
Next Jointing Requirements (screwed pipe fittings and unions)